: +86 18959610089 ( WeChat&Whatsapp )    : ym02@zzql.com 

What Are the Requirements for Smoke Curtains in an Elevator?

Views: 896     Author: Site Editor     Publish Time: 2026-02-27      Origin: Site



## Introduction


Elevator smoke curtains are critical life-safety devices designed to prevent smoke migration through elevator shafts during fires. In modern high-rise buildings, elevator shafts act as vertical "chimneys," potentially drawing smoke and toxic gases from a fire floor to upper levels, endangering occupants throughout the structure .


Smoke inhalation causes more than 70% of fire-related deaths, making smoke containment systems not just a code requirement but a life-saving necessity . This comprehensive guide explains the exact requirements for elevator smoke curtains under the International Building Code (IBC), NFPA standards, and testing protocols that manufacturers and building owners must follow.


**Primary Keywords:** elevator smoke curtain requirements, hoistway smoke containment, IBC Section 3006, NFPA 80 smoke curtains, UL 1784 testing



## Section 1: Regulatory Framework and Code Basis


### When Are Elevator Smoke Curtains Required?


Under the **International Building Code (IBC) Section 3006.3**, protection of elevator hoistway door openings is required in specific building types, particularly high-rise structures. The code provides five compliance options, and smoke curtains are explicitly recognized as one acceptable method :


> "A smoke-protective curtain assembly for hoistways shall be provided at each elevator hoistway door opening in accordance with Section 3002.6. Such curtain assemblies shall comply with the smoke and draft control requirements in Section 716.2.2.1.1 when tested in accordance with UL 1784 without an artificial bottom seal" .


### The Five Compliance Pathways


IBC Section 3006.3 allows building designers to choose among five methods for hoistway smoke protection :


| Method | Description |

|--------|-------------|

| **1. Enclosed elevator lobby** | Fire partitions separating hoistway from each floor |

| **2. Smoke partition lobby** | Smoke partitions (requires sprinkler system) |

| **3. Additional doors** | Smoke and draft control doors at each hoistway opening |

| **4. Hoistway pressurization** | Mechanical pressurization per Section 909.21 |

| **5. Smoke-protective curtain** | Deployable curtain assembly meeting UL 1784 requirements |


For buildings exceeding **75 feet in height**, IBC Section 3008 specifically requires elevator lobby protection, and smoke curtains offer a space-efficient compliance solution .



## Section 2: Testing and Performance Requirements


### UL 1784: The Critical Standard


The most fundamental requirement for elevator smoke curtains is compliance with **UL 1784**, the Standard for Air Leakage Tests of Door Assemblies. The code specifically requires testing "without an artificial bottom seal," meaning the curtain's sealing performance must be inherent to the system design .


Key UL 1784 performance metrics include :


- **Maximum air leakage:** 0.015 m³/(s • m²) (3 cf/min/sq ft) of opening

- **Test pressure:** 24.9 Pa (0.10 inches of water)

- **Test conditions:** Both ambient temperature and elevated temperature exposure


### Control Unit Requirements


Smoke curtain assemblies must be equipped with a **control unit listed to UL 864**, the Standard for Control Units and Accessories for Fire Alarm Systems . This ensures reliable integration with the building's fire alarm system.


### Deployment Speed Requirements


NFPA 80 specifies operational parameters for hoistway smoke curtains :


- **Average closing speed:** Between 152 mm (6 inches) and 610 mm (24 inches) per second

- **Activation timing:** Must deploy within 10 seconds of alarm activation


### Temperature Resistance


Elevator smoke curtains must withstand elevated temperatures while maintaining functionality. Typical requirements include :

- **Smoke resistance:** Withstand 200°F+ temperatures

- **Fire endurance:** 30-120 minute ratings depending on application (EI30 to EI120)



## Section 3: Installation Requirements


### Clearance and Fit


NFPA 80 mandates strict clearance requirements for smoke curtain installations :


- **Maximum gaps:** 1/4 inch or less at sides and top

- **Bottom seal:** Must effectively seal against the floor or threshold


The curtain assembly must be installed in accordance with the manufacturer's listed installation instructions and comply with ASME A17.1 (Standard for Elevators and Escalators) .


### Power and Backup Requirements


Elevator smoke curtains require reliable power sources :


- **Primary power:** 24V DC or building electrical system

- **Backup power:** Battery backup capable of multiple deployment cycles

- **Duration:** Some systems provide up to 10 hours of standby operation


Cornell's SmokeShield® system, for example, includes integrated battery backup ensuring continued operation during power outages .


### Physical Size Limitations


Most elevator smoke curtain systems can accommodate openings up to :

- **Width:** Up to 12 feet (3.66 meters)

- **Height:** Up to 12 feet (3.66 meters)

- **Headroom:** Compact designs require less than 10 inches of overhead space when retracted



## Section 4: Acceptance Testing and Inspection


### Initial Acceptance Testing


Per NFPA 80 Section 5.2.3, acceptance testing must be performed by a qualified person with knowledge of the operating components . The testing includes:


1. **Visual inspection** for damaged, field-modified, or missing parts

2. **Verification of labels** and listing marks

3. **Mounting and assembly component inspection**

4. **Hoistway smoke detector verification**

5. **Auxiliary hardware inspection**


### Operational and Drop Testing


Following installation, operational testing must verify :

- Proper deployment upon signal

- Correct closing speed

- Complete sealing at full extension

- Proper retraction and resetting


All inspection and testing documentation must be signed by a witness and kept for inspection by the authority having jurisdiction (AHJ) for the life of the assembly .



## Section 5: Periodic Inspection and Maintenance


### Annual Requirements


NFPA 80 mandates **annual inspection and drop testing** for all smoke curtain assemblies . The periodic testing includes:


- Visual inspection of all components

- Operational evaluation

- Full drop test

- System reset verification

- Emergency power source testing


### Maintenance Responsibilities


Building owners and property managers are responsible for :

- Completing repairs without delay

- Using only qualified professionals for maintenance

- Replacing entire assemblies if beyond repair or if original parts unavailable


### Common Compliance Mistakes


Avoid these frequent errors :

- ❌ Ignoring local amendments (e.g., seismic bracing requirements in California)

- ❌ Skipping annual inspections

- ❌ Using non-certified curtains (voids insurance coverage)

- ❌ Improper clearance gaps exceeding 1/4 inch



## Section 6: Certification and Listing Requirements


### Required Certifications


For North American projects, elevator smoke curtains must carry :


- **UL Listing:** UL 1784 for smoke leakage, UL 325 for safety

- **ICC-ES AC77 compliance:** Acceptance criteria for smoke-containment systems

- **NFPA 80 compliance:** Installation and maintenance standards


California projects have additional requirements, including California State Fire Marshal approval and compliance with Title 24 seismic provisions .


### Labeling Requirements


Smoke and draft control assemblies complying with UL 1784 must include the letter **"S"** on the fire-rating label, indicating the assembly meets smoke leakage requirements .



## Section 7: International Requirements


### European Standards (EN)


For EU projects, elevator smoke curtains must comply with :

- **EN 12101-1:** Smoke and heat control systems

- **CE marking:** Mandatory for EU sales

- **Minimum airflow:** ≥0.25 m/s to block smoke


### Other Regional Requirements


- **United Kingdom:** BS 8524 standards apply

- **Middle East:** UAE Civil Defense requires 30-minute integrity (EI30)

- **Singapore:** Fire Code aligns with BS 8524



## Section 8: Special Applications and Considerations


### Existing Building Retrofits


When altering existing buildings, the International Existing Building Code (IEBC) may trigger smoke curtain requirements even if the elevator itself isn't modified. Level 2 alterations in high-rise buildings can require installation of smoke curtains or lobbies .


### Firefighter Operations


Modern elevator smoke curtains include features for emergency responder access :

- **Curtain-mounted pressure switches:** Allow firefighters to open the curtain when needed

- **Automatic resealing:** Curtain closes and reseals after a ten-second delay

- **Manual override:** ADA-compliant emergency strap on the bottom bar



## Section 9: How to Choose a Compliant Elevator Smoke Curtain


### Certification Checklist


When selecting an elevator smoke curtain, verify :


- [ ] UL 1784 listing without artificial bottom seal

- [ ] UL 864 listed control unit

- [ ] ICC-ES AC77 compliance

- [ ] NFPA 80 installation compliance

- [ ] Local amendments (seismic, etc.)


### Design Considerations


Work with manufacturers to ensure :

- Proper sizing for your opening (width/height)

- Adequate headroom for housing

- Aesthetic integration with architecture

- Battery backup capacity



## Conclusion: Summary of Key Requirements


Elevator smoke curtains are non-negotiable life-safety components governed by a comprehensive framework of codes and standards. The essential requirements include:


1. **IBC Section 3006.3 compliance** as one of five acceptable protection methods

2. **UL 1784 testing** with maximum 0.015 m³/(s • m²) air leakage

3. **UL 864 listed control unit** for fire alarm integration

4. **NFPA 80 installation and maintenance** compliance

5. **Annual inspection and drop testing** by qualified personnel

6. **Proper clearance** (≤1/4 inch gaps)

7. **Reliable power source** with battery backup

8. **Clear labeling** with "S" designation


Building owners, architects, and facility managers must prioritize products with proper certifications, professional installation, and regular maintenance to ensure these critical systems function when needed most. The consequences of non-compliance extend beyond code violations to potentially life-threatening failures during actual fire events.


Facebook
Twitter
LinkedIn
Instagram
WELCOME
"safety +AI+ insurance + service"
  • Expert for rolling door motor and smoke curtain system

  • Whatsapp & Cellphone
    +8618959610089