SMOKE & FIRE CURTAIN SOLUTIONS – QUICK SPEC SHEET


1. What they do  

  • Fire curtain: 1–4 h fire resistance; blocks flames & hot gases.  

  • Smoke curtain: 30–120 min smoke-tight; channels toxic smoke toward extraction.  

  • Combined curtain: single barrier certified for both fire and smoke (EN 12101-1 / BS 8524 / UL 10D).


2. Typical makeup  

  – Curtain fabric: e-glass + stainless thread + silicone or PU coating, 400–900 g/m².  

  – Roller box: 0.8–1.2 mm galvanized or stainless steel, 200–350 mm Ø.  

  – Side guides: 1.5 mm steel or aluminium with intumescent smoke-seal brush.  

  – Drive: 24 V DC tubular motor with integrated brake; battery back-up 30–90 min.  

  – Release: fusible link 68 °C, or signal from fire panel (FSA / FSC), 0.2 m/s descent.


3. Sizes (single span)  

  Width up to 8 m (smoke) or 6 m (fire); height up to 10 m without intermediate support.  

  Larger openings → multiple curtains overlapped 100 mm or side-by-side with 50 mm gap sealed.


4. Controls & interface  

  • Normally held retracted by electromagnetic brake; failsafe gravity closure.  

  • Feedback: open/closed limit switches + curtain-in-position volt-free contacts.  

  • Integrates with any addressable fire alarm; supports BACnet/Modbus gateway if BMS required.


5. Certification snapshot  

  – Fire integrity: EW 60 / EI 120 (EN 13501-2) or UL 10D 2 h.  

  – Smoke leakage: S 600 (–20 Pa) ≤ 5 m³/h·m (EN 12101-1).  

  – Cyclic durability: ≥ 2 000 cycles (EN 14600).


6. Where used  

  • Atrium separation, escalator surrounds, lift-door protection, open-plan office compartments, corridor sub-division, kitchen-to-public boundary, museum voids, airport piers.


7. Installation notes  

  • Box recessed in ceiling or surface-mounted; allow 150 mm clearance for maintenance.  

  • Minimum 500 mm free space above box for fabric rewind.  

  • Power: 230 V AC supply converted to 24 V DC; battery pack inside control panel.  

  • Commissioning: drop-test, speed check (0.05–0.20 m/s), side-guide tightness, alarm interface.


8. Maintenance  

  Six-monthly drop-test and fabric visual; annual full-drop with load test & battery duration check. Record in site fire-safety logbook.



9. Budgetary pricing (FOB Shanghai, Q4 2025)  

   Smoke curtain: USD 90–130 / m²  

   Fire curtain EI120: USD 160–220 / m²  

   Control panel & battery: USD 450–600 set  

   *Final cost scales with quantity, fabric grade, finish, local certification.*


Need a project-specific schedule, dwg detail or UL certificate? Let me know the opening size and fire-rating requirement and I’ll pull the exact model numbers.